ANALISIS PENGARUH FAKTOR DAYA TERHADAP DROP TEGANGAN DAN RUGI DAYA PENYULANG PUNCAK MUNDI MENGGUNAKAN ETAP 12.6 DI PT PLN (PERSERO) ULP KLUNGKUNG
Keywords:
Drop voltage, Losses, Power Factor, Feeder, ETAP 12.6Abstract
Losses are the energy lost in power distribution which the value is directly proportional to the line impedance value and the load. Losses and power factor are related to the large amount of inductive load which eventually causes a voltage drop. Drop voltage measured at Puncak Mundi is 5.2% which exceeded the voltage drop limit according to the SPLN 72:1987 standard, which is 5%. So that a reconfiguration simulation is carried out which results a decrease in the voltage drop to 2.76% and it is also known that there is an increase in the value of the feeder power factor. In this paper, research on the load flow of Puncak Mundi Feeder was carried out with two schemes, which using a power factor of 0.89 and 0.95 to know the effect of power factor on the value of voltage drop and losses. From the simulation results, it was found that there was an increase in electrical energy efficiency with a power factor value of 0.95 compared to 0.89. The percentage of voltage drop decreased from 2.76% to 2.06% and the percentage of power loss also decreased from 4.80% to 4.49%.
References
Agu, S. B., & Gianto, R. (2022). Evaluasi Perbaikan Losses dan Faktor Daya pada Jaringan Listrik PT Wilmar Cahaya Indonesia Tbk-Pontianak. Jurnal Teknik Elektro Universitas Tanjungpura, 2(1).
Dani, A., & Hasanuddin, M. (2018). Perbaikan Faktor Daya Menggunakan Kapasitor Sebagai Kompensator Daya Reaktif (Studi Kasus Stt Sinar Husni). Seminar Nasional Royal (SENAR), 1(1), pp. 673-678.
Hidayat, N., & Muslimin, S.Y. (2020). Simulasi Sistem Perbaikan Faktor Daya (Power Factor Correction, PFC) Menggunakan Perangkat Lunak PSCAD. (Skripsi, Universitas Muhammadiyah Makassar, 2020) Diakses dari: https://digilibadmin.unismuh.ac.id/upload/12437-Full_Text.pdf
Hontong, N. J., Tuegeh, M., & Patras, L. S. (2015). Analisa rugi–rugi daya pada jaringan distribusi di PT. PLN Palu. Jurnal Teknik Elektro dan Komputer, 4(1), 64-71.
Kurniawan, R. T., & Supardi, A. (2020). Analisis Hasil Pengukuran Beban dan Rugi-Rugi Daya pada Jaringan Distribusi Tegangan Menengah di Area Boyolali (Doctoral dissertation, Universitas Muhammadiyah Surakarta). Diakses dari: http://eprints.ums.ac.id/id/eprint/80372
Noor, F. A., Ananta, H., & Sunardiyo, S. (2017). Pengaruh Penambahan Kapasitor Terhadap tegangan, arus, faktor daya, dan daya aktif pada beban listrik di minimarket. Jurnal Teknik Elektro, 9(2), 66-73.
Octary, W., Eteruddin, H., & Tanjung, A. (2020). Susut Tegangan pada Penghantar ACCC di Saluran Transmisi 150 kV di PT. PLN (Persero) Unit Pelayanan Transmisi Pekanbaru. SainETIn: Jurnal Sains, Energi, Teknologi, dan Industri, 5(1), 1-7.
Putri, M., & Pasaribu, F. I. (2018). Analisis Kualitas Daya Akibat Beban Reaktansi Induktif (XL) di Industri. JET (Journal Of Electrical Technology), 3(2), 81-85.
Suardika, I. P. A., Arjana, I. G. D., & Pemayun, A. A. G. M. (2018). Rekonfigurasi Saluran Distribusi 20 kV Untuk Mengurangi Rugi-Rugi Daya dan Jatuh Tegangan Pada Penyulang Abang. Jurnal SPEKTRUM, 5(2), 231-238.
Ulinuha, A., & Widodo, W. A. (2018). Rancang Bangun Pembangkit Listrik Tenaga Angin Skala Mikro Untuk Keperluan Penerangan Jalan. Proceeding of The URECOL, 128-135.
Ulya, A. U. (2019). Analisis Dan Simulasi Pengaruh Pemasangan Capasitor Bank Untuk Perbaikan Faktor Daya Menggunakan Simulink Pada Sistem Tenaga Listrik Di PT. Bogowonto Primalaras. Media Elektrika, 12(1), 1-11.
Yuliastuti, N. A. (2021). Penggunaan Capacitor Bank untuk Kompensasi Daya Reaktif Rumah Sakit di Yogyakarta (Doctoral dissertation, Universitas Muhammadiyah Surakarta). Diakses dari: http://eprints.ums.ac.id/id/eprint/93196